Temperature during storage/transport -30 to +65/70 °C (-22 to +149/158 °F)
Maximum altitude above sea level without derating 1000 m (3281 ft)
Maximum altitude above sea level with derating 3000 m (9842 ft)
Derating for high altitude, see chapter 6.3.2 Derating for Low Air Pressure and High Altitudes
Safety standards EN/IEC 61800-5-1, UL 508C
EMC standards, Emission EN 61800-3, EN 61000-6-3/4, EN 55011, IEC 61800-3
EMC standards, Immunity
EN 61800-3, EN 61000-3-12, EN 61000-6-1/2, EN 61000-4-2, EN 61000-4-3, EN 61000-4-4,
EN 61000-4-5, EN 61000-4-6
Energy efficiency class IE2
1) Refer to special conditions in the design guide for:
•
Derating for high ambient temperature
•
Derating for high altitude
2) Determined according to EN50598-2 at:
•
Rated load
•
90% rated frequency
•
Switching frequency factory setting
•
Switching pattern factory setting
Specifications VLT®HVAC Basic Drive FC 101
58 Danfoss A/S © 08/2014 All rights reserved. MG18A622
66