Mounting and installation instructions, continued
Self-production of
chlorine
The following guidance values are applicable to swimming pools with self-production of
chlorine:
Chemicals
ppm
Salt (NaCl)
2700-3400
Total dissolved solids
< 5500
pH
7,2-7,6
Total alkalinity
80-150
Calcium hardness
250-450
Sulphates
< 360
Langelier Saturation
index
It is advisable to use the Langelier Saturation index to ensure that the combination of
the different water parameters is acceptable.
Contact Dantherm Air Handling A/S if necessary.

Table of Contents