EasyManua.ls Logo

Dantherm CS030040B - Initiating the TEST Sequence; Resetting Controller to Factory Defaults

Dantherm CS030040B
17 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Air Conditioner 4000 Installation, Operating & Maintenance Manual
AC-4 CS030040 4K Manual Rev D Page 10 of 17
5.5.2 Initiating the “TEST” sequence
1. Press L button for 2 seconds and release (Display will begin “Display Mode”)
2. Press L&R button simultaneously for 2 seconds and release (Display will show “test”)
3. Press L button for 2 seconds and release (Display will show test step)
4. TEST steps
STEP
DESCRIPTION
LED
INT.
FAN
HEATER
COMP
COND.
FAN
DURATION
0
Display S/W Revision Level
X.XX
ON
OFF
OFF
OFF
10 SEC
1
Int. Fan only
T01
ON
OFF
OFF
OFF
30 SEC
2
Heater
T02
ON
ON
OFF
OFF
35 SEC
3
Int. Fan only
T03
ON
OFF
OFF
OFF
20 SEC
4
Con Fan
T04
ON
OFF
OFF
Cycle
30 SEC
5
Comp. and cond.
T04
ON
OFF
ON
ON
75 SEC
6
Int. Fan only
T05
ON
OFF
OFF
OFF
30 SEC
5.5.3 Resetting the controller to factory defaults
1. Ensure return temperature is displayed otherwise wait 30 seconds
2. Press L&R button for 15 seconds and release (Display will show “----”)