AC-6 iAC 6K 8K Manual Rev B Page 1 of 22
Dantherm, Inc.
110 Corporate Drive, Suite K
Spartanburg, SC 29303
Tel # +1 864 595 9800
Fax # +1 864 595 9810
Email: dantherm.usa@dantherm.com
Website: www.dantherm.com
Panel Mounted Air Conditioners
by Dantherm Inc.
iA/C T-Series
iA/C T-A6000, -B6000, -B8000
with USACG-6 Control
PRODUCT INFORMATION MANUAL

Other manuals for Dantherm iA/C T Series

Questions and Answers

  • B
    Brian CastilloAug 19, 2025
    Why is my Dantherm Air Conditioner not cooling sufficiently?
    • H
      Hailey CarterAug 19, 2025
      If your Dantherm Air Conditioner isn't cooling sufficiently, several factors could be the cause. First, check the filter, if your unit has one, to ensure it's not clogged; clean or replace it if necessary. Next, inspect the evaporator and condenser coils for any blockage and clean them. Also, verify that the evaporator or condenser blower is functioning correctly; if not, you may need to replace the motor, capacitor, or the entire assembly. Finally, check for refrigerant or oil leaks, locate and repair any leaks, and replace the charge.
  • C
    Colleen WilliamsAug 21, 2025
    What to do if my Dantherm Air Conditioner is not running?
    • N
      Nicholas OwensAug 21, 2025
      If your Dantherm Air Conditioner isn't running, begin by checking the power source and all electrical connections to ensure they are properly connected. Then, inspect the control board for a blown fuse and replace it if necessary. If these steps don't resolve the issue, perform a self-test to identify any faulty control components.
  • J
    Joel ClarkAug 25, 2025
    How to troubleshoot a Dantherm iA/C T that is not running?
    • N
      nelsonmaryAug 25, 2025
      If your Dantherm Air Conditioner isn't running, there are several potential causes. First, check the power source and electrical connections to ensure they are properly connected. If the power source is okay, inspect the control board for a blown fuse and replace it if necessary. Finally, faulty control components might be the root cause, in that case you should carry out a self test.
  • E
    Emily IbarraAug 26, 2025
    Why is my Dantherm iA/C T Air Conditioner not cooling enough?
    • E
      Elizabeth ByrdAug 26, 2025
      If your Dantherm Air Conditioner isn't cooling sufficiently, it could be due to several reasons. Check the filter (if applicable) and clean or replace it if it's clogged. Inspect the evaporator or condenser coil for blockage and clean it if necessary. Ensure that the evaporator or condenser blower is operating correctly; if not, consider replacing the motor, capacitor, or the entire assembly. Another potential cause is a loss of refrigerant or oil leaks, which would require locating and repairing the leak and replacing the refrigerant charge. For insufficient capacity, contact Dantherm Air Handling, Inc.
  • T
    Timothy FreemanAug 28, 2025
    What to do if Dantherm iA/C T displays Missing Compressor Current (F=01)?
    • J
      Jesus HammondAug 28, 2025
      If your Dantherm Air Conditioner shows a 'Missing Compressor Current (F=01)' error, it could be due to a few reasons. First, check the wiring to ensure it is securely and properly installed according to the diagram. If the wiring is correct, the current sensor might be broken, requiring replacement of the control board. Lastly, the compressor itself might be faulty and need replacement.
  • H
    hayskristenAug 30, 2025
    How to fix High Pressure Alarm (F=02) on Dantherm Air Conditioner?
    • H
      Holly StarkAug 30, 2025
      If your Dantherm Air Conditioner displays a 'High Pressure Alarm (F=02)', the issue might stem from a faulty condenser fan or loose wiring, in which case you should replace the fan or check the wiring. Alternatively, a faulty condenser fan capacitor or loose wiring could be the cause, requiring replacement of the capacitor or checking the wiring. Lastly, the problem could be a faulty condenser fan switch or high-pressure switch, necessitating replacement of the appropriate switch.
  • O
    omcguireSep 1, 2025
    Why is there ice on the evaporator coil of my Dantherm iA/C T Air Conditioner?
    • R
      Robert MataSep 1, 2025
      Ice forming on the evaporator coil of your Dantherm Air Conditioner can be due to a couple of reasons. It could be caused by insufficient heat load or the unit being oversized for the application, in this case contact Dantherm Air Handling, Inc.. Alternatively, a failed evaporator blower might be the culprit, requiring replacement of the evaporator blower motor or assembly.
  • R
    Richard JohnstonSep 3, 2025
    What causes Low Pressure Alarm before start (F=04) in Dantherm Air Conditioner?
    • J
      James FischerSep 3, 2025
      If your Dantherm Air Conditioner shows a 'Low Pressure Alarm before start (F=04)', it's likely due to either no refrigerant in the system (possibly from a large leak) or a low charge in the system. In either case, you should locate and repair the leak, then replace the refrigerant charge.
  • C
    Christopher PollardSep 6, 2025
    What does Low Pressure Alarm after start (F=03) mean on Dantherm iA/C T Air Conditioner?
    • M
      Michael HughesSep 6, 2025
      If your Dantherm Air Conditioner displays a 'Low Pressure Alarm after start (F=03)', it is probably caused by a slow leak in the system. To solve it you should locate and repair the leak and then replace the charge.
  • U
    uperezSep 8, 2025
    What to do for Faulty Temperature Sensor (F=07) on Dantherm iA/C T Air Conditioner?
    • S
      Sarah TurnerSep 8, 2025
      If your Dantherm Air Conditioner displays a 'Faulty Temperature Sensor (F=07)' error, there are a couple of potential causes. First, check if the sensor is properly connected and reconnect it if necessary. If the connection is secure, the sensor itself might be faulty and need replacement.

Summary

1 General Safety & Warning Instructions

4 Dimensions & Installation

4.4 Installation and Connections

Procedure for connecting the air conditioner to power and other necessary systems.

4.5 Unit Operation

Steps to initiate and verify the basic operation of the air conditioner unit.

5 USACG-6 Intelligent Controller Operation

5.5 Debugging the System

Methods for diagnosing issues, observing fault codes, and initiating test sequences.

6 Maintenance

6.1 Preventative Maintenance Schedule

A detailed schedule outlining recommended preventative maintenance tasks and frequencies.

6.6 Troubleshooting

A chart listing common problems, potential causes, and solutions for the air conditioner.

6.9 Wiring Diagram

Electrical wiring diagrams for the air conditioner units, including specific models.