Controller CC3000
How to:
Check correct installation.
After installation of controller and cooling product, correct connectivity can be checked by use
of a selftest function. > See manual for CC3000.
If automatic sequence is started, controller will activate all outputs one by one.
Time duration for each step is 3 minutes, which should be sucient for the installer to check
that fans, dampers, air conditioners, heaters and alarms are
correctly connected.
Test steps can be bypassed by pressing down key.
A manual sequence can also be used, if only certain outputs are checked.
Use up/down key to select output and press enter. Output is now activated.
Pressing enter again, will deactivate output.
After connectivity check, go to main menu and check that indoor/outdoor temperature reading
is correct and that set point is correct.
If shelter temperature is below set point, indoor temperature sensor can be heated by hand, to
check that fan starts when temperature reach set point.
Note: If sensor temperature reach air conditioner set point and air conditioner is started, it has a
minimum runtime of 3 minutes.