27
Default Cooling strategies (can be changed using the CC3000 controller. )
Description Value
O
Temperature when fan stops
20
On
Temperature when Fan starts
23
Min °C
Temperature at bottom of P-band
25
Max °C
Temperature at top of P-band
29
Set Point
The wanted indoor temperature; fan speed will
be adjusted between Min°C and Max °C
27
A/C 1 on
External Air Con unit 1 start if connected
31
A/C 1 o
External Air Con unit 1 stops if connected
29
A/C 2 on
External Air Con unit 2 start if connected
33
A/C 2 o
External Air Con unit 2 stops if connected
31
Emergency on
Fan run 100% and both A/C 1 and A/C 2 starts
38
Emergency o
Fan stops both A/C 1 and A/C 2 continue to run
36
Standard Mode
(Freecooling <> A/C)
A/C unit 1 start at set point if outdoor temperature is less than 3°K colder than set point.
If outdoor temperature is more than 3°K colder than setpoint the A/C unit 1 will start at 31°C