28
Description Value
O temperature when fan stops 20
On Temperature when Fan starts 23
Min °C temperature at bottom of P-band 25
Max °C Temperature at top of P-band 29
Set Point
The wanted indoor temperature; fan
speed will be adjusted between Min°C
and Max °C
27
A/C 1 on
External Air Con unit 1 start if connected
31
A/C 1 o
External Air Con unit 1 stops if connected
29
A/C 2 on
External Air Con unit 2 start if connected
33
A/C 2 o
External Air Con unit 2 stops if connected
31
Emergency on
Fan run 100% and both A/C 1 and A/C 2 starts
38
Emergency o
Fan stops both A/C 1 and A/C 2 continue to run
36
Energy save Mode
(Freecooling > A/C)
If outdoor temperature is less than 1°C colder than indoor room temperature the Flexibox
Fan will stop.
The connected Air-con units will start and stop according to the table above.