Errors are indicated by the LED, placed below the filter reset button.
If this LED is flashing slowly with a orange color, please exchange the air filters. See
section “Replace filters” at page 33
LED readings
Software <2.0
If this LED is red, it indicates an operation error. This red LED can indicate three differ-
ent levels of errors:
Bypass damper fail
T3/T4 internal temperature sensor fail
Internal fan failure
Supply temperature is <+5°C
External fire alarm activated
Any internal sensor is measuring a temperature >70°C
T1/T2 temperature sensor defective
LED readings
Software ≧2.0
If this LED is flashing red, it indicates an operation error. The LED will flash a number of
times that equals the corresponding error code, followed by a pause of five seconds,
before restarting the counting again. The error code counts, corresponds to the below
following errors:
Error number
Remote control
Extract air temperature sensor (T1)
Supply air temperature sensor (T2)
Extract air temperature sensor (T3)
Exhaust air temperature sensor (T4)
Room air temperature sensor (T5)
Humidity sensor, RH% (Accessory)
Outdoor temperature < -13 °C
Supply temperature < +5 °C
Fire alarm, any one of the internal sensor, is measuring
a temperature > 70 °C.
Communication error / low signal
Fire alarm, duct connected fire thermostat (Accessory)
VOC sensor fail (Accessory)