Technical data TKS 60
Free cooling perfor-
mance
The table below shows the performance of the free cooling unit:
Specification
230 V B ver.
48 V DC
M5 filter
F7 filter
M5 filter
F7 filter
Air flow m
3
/h
4285
4010
3200
2940
Cooling effect W/K
1424
1333
1063
977
Cooling effect at
Δt=5°C
7.1 kW
6.7 kW
5.3 kW
4.9 kW
Power
consumption
782 W
773 W
389 W
405 W
Acoustic pressure
~82.3dBA
~78.2dBA
External available
pressure drop
150 Pa
150 Pa
Unit data
Data and dimensions of the free cooling unit are shown in the table below:
Specification
Cover
Value
Weight
Estimated max
60 kg
Constituent plate components
Zinc aluminium AZ150
0.9-2.0 mm
Frame
Aluminium
1.5 mm (minimum thickness)
External sandwich panels
Painted galvanised steel
plate (Grey color. RAL
9002)
0.5 mm
Internal sandwich panels
Galvanised steel plate
0.5 mm
Insulation in sandwich panels
Polyurethane
25 mm
Filter data
The table below shows data for the filter.
Filter
Type
Class
Dimension
Filter guard
setting
087363 / 405512
Bag filter, 9 bags
M5
IF45stø:540x487x535
250 Pa
087364 / 405414
Bag filter, 8 bags
F7
IF80 stø:540x487x535
250 Pa