5
Standard Fluid Cooler Selection Chart
All selections based on 40% Glycol
Ambient Temperature
95 100 105
1
Fluid PD Fluid PD Fluid PD
Model THR GPM Cooler MBH (FT) Cooler MBH (FT) Cooler MBH (FT)
Mini Ceiling
DAM* 01 15 3.5 DAFC 06 31 0.2 DAFC 06 25 0.2 DAFC 06 19 0.2
DAM* 1.5 23 5.3 DAFC 06 38 0.5 DAFC 06 30 0.5 DAFC 06 23 0.5
DAM* 02 30 7.0 DAFC 06 49 1.1 DAFC 06 39 1.1 DAFC 09 36 1.6
DAM* 2.5 36 8.8 DAFC 06 57 1.6 DAFC 06 45 1.6 DAFC 09 42 2.5
Mini Plus
DAP* 2.5 39 8.8 DAFC 06 57 1.6 DAFC 06 45 1.6 DAFC 09 42 2.5
DAP* 03 49 10.5 DAFC 06 63 2.2 DAFC 06 50 2.2 DAFC 09** 46 3.4
DAP* 04 72 14.0 DAFC 06 72 3.7 DAFC 09** 71 5.7 DAFC 28** 68 0.3
DAP* 05 88 17.5 DAFC 07 89 7.1 DAFC 15** 87 1.1 DAFC 30 94 1.8
Large Ceiling Units - Single Compressor
DAL* 06 104 21 DAFC 11 104 3.0 DAFC 17** 102 0.9 DAFC 30 108 2.5
DAL* 08 136 28 DAFC 15 139 2.5 DAFC 21 147 3.3 DAFC 37 137 2.3
DAL* 10 181 35 DAFC 21 207 5.0 DAFC 28 182 1.9 DAFC 50 183 2.9
DAL* 13 230 46 DAFC 21 233 8.2 DAFC 30 232 10.1 DAFC 50** 220 4.7
Large Ceiling Units - Dual Compressors
DAL* 06 103 21 DAFC 11 104 3.0 DAFC 17** 102 0.9 DAFC 30 108 2.5
DAL* 08 138 28 DAFC 15 139 2.5 DAFC 21 147 3.3 DAFC 37** 137 2.3
DAL* 10 174 35 DAFC 21 207 5.0 DAFC 24 175 2.8 DAFC 44 179 4.1
DAL* 13 224 46 DAFC 21 233 8.2 DAFC 30 232 10.1 DAFC 50** 220 4.7
Data Temp
DT*D/U 02 36 7.0 DAFC 06 49 1.1 DAFC 06 39 1.1 DAFC 09 36 1.6
DT*D/U 03 49 10.5 DAFC 06 63 2.2 DAFC 06 50 2.2 DAFC 09** 46 3.4
DT*D/U 04 72 14.0 DAFC 06 72 3.7 DAFC 09** 71 5.7 DAFC 28** 68 0.3
DT*D/U 05 88 17.5 DAFC 07 89 7.1 DAFC 15** 87 1.1 DAFC 30 94 1.8
Modular Data Temp
DT*D/U 08 136 28 DAFC 15 139 2.5 DAFC 21 147 3.3 DAFC 37 137 2.3
DT*D/U 10 172 35 DAFC 21 207 5.0 DAFC 24 175 2.8 DAFC 44 179 4.1
DT*D/U 13 224 46 DAFC 21 233 8.2 DAFC 30 232 10.1 DAFC 50** 220 4.7
Data Aire Series
DA*D/U 06 100 21 DAFC 11 104 3.0 DAFC 17 102 0.9 DAFC 30 108 2.5
DA*D/U 08 146 28 DAFC 17 148 1.4 DAFC 21 147 3.3 DAFC 44 152 2.8
DA*D/U 10 162 35 DAFC 17 163 2.1 DAFC 21 166 5.0 DAFC 40 164 2.4
DA*D/U 13 224 46 DAFC 21 233 8.2 DAFC 30 232 10.1 DAFC 50** 220 4.7
DA*D/U 16 245 56 DAFC 24 269 6.5 DAFC 30 247 14.4 DAFC 50 245 6.7
DA*D/U 20 310 70 DAFC 37 360 12.1 DAFC 40** 304 8.4 DAFC 75 317 3.5
DA*D/U 26 387 91 DAFC 40 404 13.4 DAFC 50 393 16.0 DAFC 88 422 6.6
DA*D/U 30 482 105 DAFC 50 509 20.7 DAFC 61 483 12.8 DAFC 100** 475 6.0
gForce GT
GT*D/U007 36 7.0 DAFC 06 49 1.1 DAFC 06 39 1.1 DAFC 09 36 1.6
GT*D/U011 49 10.5 DAFC 06 63 2.2 DAFC 06 50 2.2 DAFC 09** 46 3.4
GT*D/U014 72 14.0 DAFC 06 72 3.7 DAFC 09** 71 5.7 DAFC 28** 68 0.3
GT*D/U018 88 17.5 DAFC 07 89 7.1 DAFC 15** 87 1.1 DAFC 30 94 1.8
gForce
GF*D/U021 100 21 DAFC 11 104 3.0 DAFC 17 102 0.9 DAFC 30 108 2.5
GF*D/U028 146 28 DAFC 17 148 1.4 DAFC 21 147 3.3 DAFC 44 152 2.8
GF*D/U035 162 35 DAFC 17 163 2.1 DAFC 21 166 5.0 DAFC 40 164 2.4
GF*D/U046 224 46 DAFC 21 233 8.2 DAFC 30 232 10.1 DAFC 50** 220 4.7
GF*D/U056 245 56 DAFC 24 269 6.5 DAFC 30 247 14.4 DAFC 50 245 6.7
GF*D/U070 310 70 DAFC 37 360 12.1 DAFC 40** 304 8.4 DAFC 75 317 3.5
GF*D/U091 387 91 DAFC 40 404 13.4 DAFC 50 393 16.0 DAFC 88 422 6.6
GF*D/U106 482 105 DAFC 50 509 20.7 DAFC 61 483 12.8 DAFC 100** 475 6.0
* Insert: W - Water Cooled or G - Glycol
** The capacity of the selected uid cooler is less than the total heat rejection (THR) specied for the given unit. The result will be
slightly higher water temperatures which can cause a small decrease in unit capacity.
1 Fluid coolers are not recommended for higher ambient temperature