37
TEMPERATURE-PRESSURE CHART
R-407C R-410A
TEMPERATURE (°F) PRESSURE (PSIG) PRESSURE (PSIG)
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
55
60
65
70
75
80
85
90
95
100
105
110
115
120
125
130
135
140
145
150
43.6
44.7
45.9
47.1
48.4
49.6
50.9
52.1
53.4
54.8
56.2
57.5
58.9
60.3
61.7
63.1
64.6
66.1
67.6
69.1
70.6
72.2
73.8
75.4
77.1
106.0
116.2
127.0
138.5
150.6
163.5
177.0
191.3
206.4
222.3
239.0
256.5
274.9
294.2
314.5
335.7
357.8
380.9
405.1
430.3
89.7
91.6
93.5
95.5
97.5
99.5
101.6
103.6
105.7
107.9
110.0
112.2
114.4
116.7
118.9
121.2
123.6
125.9
128.3
130.7
133.2
135.6
138.2
140.7
143.3
156.6
170.7
185.7
201.5
218.2
235.9
254.6
274.3
295.0
316.9
339.9
364.1
389.6
416.4
444.5
474.0
505.0
537.6
571.7
607.6

Table of Contents