What to do if Data Aire Control Systems shows a Chilled Water Sensor Failure?
- SstefaniegriffinAug 2, 2025
If your Data Aire Control Systems unit displays a Chilled Water Sensor Failure, there are several potential causes. First, the sensor input may be enabled without a sensor being connected; in this case, go to Menu L – Configure I/O and change the Chilled Water Sensor (U10) Enable to Off. Another possibility is a loose connection, so check the connection and cable. Finally, the sensor itself might be faulty; use the Temperature Sensor Chart to verify the resistance of the sensor and replace it if necessary.