FACTORY SETTINGS
TEMPERATURE: 72.0°F (Temperature range: 65 - 85°F)
DEADBAND: 2.0°F (Temperature Deadband range: 2 - 5°F)
STAGE TO STAGE: 0.3°F (Stage-to-Stage range: 0.3 - 3.0°F)
ENGY SVR SETPT: 50.0°F (Setpoint range: 40.0 - 60.0°F)
DEADBAND: 1.0°F (Deadband range: 1.0 - 5.0°F)
CHANGE OVER: 2.0°F (Change over range: 2.0 - 5.0°F)
HUM SETPOINT: 50% (Humidity range: 25-70%)
HUM DEADBAND: 3% (Humidity deadband range: 1 - 15%)
If Humidity Anticipation is turned ON in humidity setting under Factory Setting (Menu J), the following page appears
for reference (non-editable):
Humidity Anticipation
HUM SETPOINT: 50%
TEMP OFFSET: - 2%
ANTICIPATION SP: 48%
To change the value of any one of the setpoint values, move the cursor by pressing the ENTER key to the desired set-
point. The cursor will ash on the input value. Press the UP or DOWN button to increase or decrease the value. Once
the desired setpoint value has been changed, press the ENTER key to move to the next setting or until the cursor is at
the top of the screen.
Exit the Setpoint Menu by pressing the Esc Key. The display screen will return to the MAIN MENU. Use the UP or
DOWN Keys to advance to another Menu or press the Esc Key to return to the normal operating mode.
Note: Changes to any MENU input will remain and can only be changed manually (as described above)
Following is a brief description of the remaining menus (C through L)
Menu C – Clock/Scheduler
The menu allows programming of night set-back, week-end or special day schedules. This is intended for use in
non-critical applications where units may be cycled off without any damage to sensitive electronic equipment. Typical
application is comfort cooling where units may be shut down during non-working hours.
Requires service level password for programming
Menu D – Input/Output
This is a view only menu. The values are factory set and only if instructed by Data Aire engineering or service person-
nel should these be changed.
Requires service level password for viewing
Menu E – Historical Data
Menu allows viewing of alarms, component runtime hours and re-setting of run times. Alarms will displayed by the
alarm name and the time, date of alarm occurrence. In addition, it will display the temperature and humidity at time of
alarm.
Requires service level password for programming

Other manuals for Data Aire dap4

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Data Aire dap4 and is the answer not in the manual?

Data Aire dap4 Specifications

General IconGeneral
BrandData Aire
Modeldap4
CategoryControl Systems