DKG-116 User Manual V-02 (
11.08.2010)
PRECAUTIONS FOR INSTALLATION AND SAFE USE
Failure to follow below instructions will result in death or serious injury.
Circuit breakers must be connected serially to BAT+, PHASE-L1, PHASE-L2 and
PHASE-L3 terminals, in close proximity of the unit.
Fuses must be of fast type with a maximum rating of 6A.
Disconnect all power before working on equipment .
When the genset is running, do not touch terminals.
Do not try to clean the device with solvent or the like. Only clean with a dried cloth.
Verify correct terminal connections when wiring.
Electrical equipment should be serviced only by competent service personnel. No
responsibility is assured by the manufacturer or any of its subsidiaries for any
consequences arising out of the use of this material.
Only for front panel mounting.
PROGRAMMING
Both High Temperature and Emergency Stop inputs must be connected to
Battery negative prior to enter the programming mode.
The unit offers 8 programmable parameters listed below.
NO
SYMBOL
RANGE
FACTORY
SET
DESCRIPTION
1
U-Lo
U-LoU-Lo
U-Lo
70-500 V 170 V Low AC voltage shutdown limit
2
U-HI
U-HIU-HI
U-HI
70-500 V 300V High AC voltage shutdown limit
3
nFrq
nFrqnFrq
nFrq
0-1 0 Nominal frequency: 0=50Hz 1=60Hz
4
OIL
OILOIL
OIL
0-1 0 Oil input: 0=pressure switch 1=level switch
5
FUEL
FUELFUEL
FUEL
0-1 0 Fuel output type 0:Fuel 1:Stop
6
r
rr
rLY3
LY3LY3
LY3
0-2 0 Relay 3 function 0:Alarm 1:Choke 2:Stop
7
CHOt
CHOtCHOt
CHOt
0-15 sec 0 Choke timer in seconds
8
3-1p
3-1p3-1p
3-1p
0-1 0 Number of phases: 0=3ph 1=1ph
The program mode is entered by long-pressing the MENU button. Each depression of the
MENU button will switch to the next parameter.
Another long press will enable the lamp test mode. Then any depression of MENU button will
return the display to normal mode.
If no key is pressed, then the unit will return to normal display mode with a delay.
DIESEL ENGINE OPTION SELECTION
In order to control diesel engines, solder a conductive wire to
JP1 terminals situated next to terminal 1, as shown in the
picture.