Program Group: Sender Characteristics (password level-2)
PGM
Parameter Definition
Unit
Fact.Set
Description
P_172
Oil Temperature Sender Ohms -1
ohm
38
Temperature Sender point 1, ohm value
P_173
Oil Temperature Value -1
°C
100
Temperature Sender point 1, °C value
P_174
Oil Temperature Sender Ohms -2
ohm
51
Temperature Sender point 2, ohm value
P_175
Oil Temperature Value -2
°C
90
Temperature Sender point 2, °C value
P_176
Oil Temperature Sender Ohms -3
ohm
134
Temperature Sender point 3, ohm value
P_177
Oil Temperature Value -3
°C
60
Temperature Sender point 3, °C value
P_178
Oil Temperature Sender Ohms -4
ohm
322
Temperature Sender point 4, ohm value
P_179
Oil Temperature Value -4
°C
39
Temperature Sender point 4, °C value
P_180
Oil Temperature Sender Ohms -5
ohm
650
Temperature Sender point 5, ohm value
P_181
Oil Temperature Value -5
°C
20
Temperature Sender point 5, °C value
P_182
Oil Temperature Sender Ohms -6
ohm
1630
Temperature Sender point 6, ohm value
P_183
Oil Temperature Value -6
°C
02
Temperature Sender point 6, °C value
Low Oil Pressure Switch Input Configuration
PGM
Parameter Definition
Unit
Fac.Set
Description
P_184
Action
0
0: Shutdown (the engine stops immediately)
1: Load Dump (the engine stops after cooldown)
2: Warning (the horn relay operates)
3: No operation
P_185
Sampling
1
0: Always
1: After holdoff timer
2: When mains present
P_186
Latching
1
0: Non latching
1: Latching
P_187
Contact type
0
0: Normally open
1: Normally closed
P_188
Switching
0
0: Battery negative
1: Battery positive
P_189
Response delay
0
0: No delay
1: Delayed (4sec)
High Temperature Switch Input Configuration
PGM
Parameter Definition
Unit
Fac.Set
Description
P_190
Action
0
0: Shutdown (the engine stops immediately)
1: Load Dump (the engine stops after cooldown)
2: Warning (the horn relay operates)
3: No operation
P_191
Sampling
1
0: Always
1: After holdoff timer
2: When mains present
P_192
Latching
1
0: Non latching
1: Latching
P_193
Contact type
0
0: Normally open
1: Normally closed
P_194
Switching
0
0: Battery negative
1: Battery positive
P_195
Response delay
0
0: No delay
1: Delayed (4sec)