EasyManua.ls Logo

Dataprobe iBootBar - Page 13

Dataprobe iBootBar
24 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
iBootBar Page 13
ibootbar_v1.2x
Outlet Commands
Description
get outlets
Returns the status of each outlet the user has
rights to.
get outlet <n>
Returns the status of outlet n
set outlet <n> <on/off/cycle>
Commands outlet n to power on/off or cycle
(reboot or power pulse)
The following commands require administrative rights.
set outlet <n> name <name>
Each outlet can be named for easy identification.
20 characters, no spaces.
get outlet <n> initial.state
set outlet <n> initial.state <last/on/off>
Set/Get the initial state of each outlet when the
iBootBar is first powered up.
get outlet <n> autoping
Returns the current AutoPing configuration for
outlet <n>
set outlet <n> autoping ipaddress <dotted decimal>
Set the IP address to be pinged for AutoPing
set outlet <n> autoping action <action>
Set the action to be performed when AutoPing is
triggered. none / on-latch / on-follow / off-
latch / off-follow / cycle / cycle-once
set outlet <n> autoping frequency <1-999>
Set the delay between ping attempts
set outlet <n> autoping count <1-99>
Set the number of failures to respond to ping
before the AutoPing feature is triggered
Timed Event Commands
Description
add event <name >
The default time and date will be the time and
date that the event is added. The default action is
none, and the default repeat is never.
del event < name >
This command removes a scheduled event from
the event list. This command functions the same
as the DEL USER and DEL GROUP commands.
ren event < name > < new name >
This command is used to rename an event that
has been scheduled.
set event < name > year < 2007 - 2050 >
This command sets the year of the event.
set event < name > month <1 - 12>
This command sets the month of the event.
set event < name > day <1 - 31>
This command sets the day of the event.
set event < name > hour < 0 - 23 >
This command sets the hour of the event.
set event < name > minute <0 - 59>
This command sets the minute of the event.
set event < name > action < on / off / cycle >
This command sets the action to take place when
the event is executed.
set event < name > repeat < never / daily / weekly / monthly / annually >
This command sets the repeat pattern for the
event.
set event < name > control < outlet / group > < n / name >
This command sets the outlet or group that will
be controlled.

Other manuals for Dataprobe iBootBar