Tab.61
On > > Installation Setup > CU-GH08 > DHW ( Internal DHW ) > Parameters, counters, signals > Parameters
Code Text display Description Adjustment range 10 15 25 25/28
MI
35
DP060 DHW timeprog.
select
Time program selected for
DHW.
0 = Schedule 1
1 = Schedule 2
2 = Schedule 3
0 0 0 0 0
DP070 DHW comfort
setpoint
Comfort temperature
setpoint from the Domestic
Hot Water tank
40 °C – 65 °C 60 60 60 55 60
DP080 DHW reduced
setpoint
Reduced temperature
setpoint from the Domestic
Hot Water tank
7 °C – 50 °C 15 15 15 15 15
DP160 DHW AntiLeg
Setpoint
Setpoint for DHW anti
legionella
50 °C – 90 °C 65 65 65 65 65
DP170 Start time holiday Start time of holiday Time
stamp
- - - - -
DP180 End time holiday End time of holiday
Timestamp
- - - - -
DP190 End change mode End change mode Time
TimeStamp
- - - - -
DP200 DHW mode DHW primary mode current
working setting
0 = Scheduling
1 = Manual
2 = Antifrost
3 = Temporary
DP337 DHW holiday
setpoint
Holiday temperature setpoint
from the Domestic Hot
Water tank
10 °C – 60 °C 10 10 10 10 10
Tab.62
On > > Installation Setup > CU-GH08 > DHW ( Internal DHW ) > Parameters, counters, signals > Parameters
Code Text display Description Adjustment range 10 15 25 25/28
MI
35
DP003 Abs. max fan
DHW
Maximum fan speed on
Domestic Hot Water
1000 Rpm 7000 Rpm 3300 4500 5600 6200 6200
DP007 Dhw 3wv Standby Position of three way valve
during standby
0 = CH position
1 = DHW position
0 1 0 1 0
DP020 Postrun DHW
pump/3wv
Post run time of the DHW
pump/3 way valve after
DHW production
0 Sec – 99 Sec 10 10 10 10 10
DP070 DHW comfort
setpoint
Comfort temperature
setpoint from the Domestic
Hot Water tank
40 °C – 65 °C 60 60 60 55 60
Tab.63
On > > Installation Setup > CU-GH08 > Outdoor sensor setup > Parameters, counters, signals > Parameters
Code Text display Description Adjustment range 10 15 25 25/28
MI
35
AP056 Outdoor sensor Enable outdoor sensor 0 = No outside sensor
1 = AF60
2 = QAC34
1 1 1 1 1
AP073 Summer Winter Outdoor temperature: upper
limit for heating
10 °C – 30 °C 22 22 22 22 22
AP074 Force summer
mode
The heating is stopped. Hot
water is maintained. Force
Summer Mode
0 = Off
1 = On
0 0 0 0 0
AP079 Building Inertia Inertia of the building used
for heat up speed
0 – 15 3 3 3 3 3
9 Settings
7686707 - v.01 - 06092018 AMC 87

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the DeDietrich AMC 15 and is the answer not in the manual?

DeDietrich AMC 15 Specifications

General IconGeneral
BrandDeDietrich
ModelAMC 15
CategoryBoiler
LanguageEnglish

Related product manuals