EasyManua.ls Logo

Deif CSQ-3 - Page 20

Deif CSQ-3
21 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 20 of 21 Tel.: (+45) 9614 9614 Fax: (+45) 9614 9615 E-mail: deif@deif.com
The length of the relay pulse t
R
can never be set to a lower value than the breaker
closing time, whereas t
R
can be set to a higher value if you want the max. slip
frequency (f) to be lower to limit the rush of current of the breaker (the generators) in
connection with the synchronising.
Example:
In the light of the above-mentioned examples t
R
is changed to 0.4 sec. With a slip
frequency (f) of 0.1Hz = 36°/sec. and t
R
= 0.4 sec. the phase changes 14.4° during
the 0.4 sec. If ∆ϕ is set to ±10° the CSQ-3 will calculate that there is space for t
R
. With
this setting the synchronising error will be identical with the synchronising error in
example 1 (-2.8°) as the breaker closing time is the same (0.2 sec.). But the max. f
can now only be 0.138Hz and not, as in example 1, 0.277Hz. The max. slip frequency
(f) could also be controlled by setting ∆ϕ differently. If ∆ϕ was set to ±5° instead of
±10° the max. f would be 0.138Hz at t
R
= 0.2 sec. With this setting and a f of 0.1Hz
the actual synchronising error will be +2.2°. Please notice that the breaker now closes
2.2° after top and not, as in example 1, 2.8° before top. The choise of setting must be
based on the knowledge of the actual installation in which the CSQ-3 is applied. But
the examples are to show that t
R
and ∆ϕ are inextricably connected and influence the
same parameters, but with different results as to the calculation of the actual
synchronising error.
If t
R
is set to infinite (∞) the max. allowable f can no longer be controlled by means of
t
R
. When t
R
is set to infinite the setting of t
d
is automatically activated. Infinite t
R
is
primarily used where the CSQ-3 is applied as supervision of an automatic
synchronising system or in connection with closing of a tie breaker where you want to
control frequency, phase and voltage to be within certain values before the breaker is
closed.
The setting of t
d
is to be calculated from ∆ϕ and the estimated max. allowable f.
(∆ϕ-) + (∆ϕ+)
t
d
=
360 x f
Example 1:
∆ϕ is set to ±7°, and a max. f of 0.05Hz at the moment of synchronising is estimated
to be allowable.
| -7 | +7
t
d
=
360 x 0.05
t
d
= 0.77 sec. ~ 0.8 sec.
Please notice that when t
R
is set to infinite (∞) the synchronising pulse (the relay
contact of the CSQ-3) is interrupted the moment the phase is outside the set phase
window. As the timer t
d
starts the moment the phase is within the set phase window