RECEIVING & STORAGE CONT.
Module Shipment
All battery accessories (connectors, terminal plates, hardware)
w
ill be included with a module pallet. The pallet will be indicat-
ed with an “Accessory” sticker. The “Accessory” module pallet
will include a base and a top plate. 3 x 2 modules will be
shipped two high with base plate and top plate on top of the
module assembly. 2 x 2 modules will be shipped 3 high with
b
ase plate & top plate on either side of the module assembly.
Cell Shipment
Each cell will be in an individual sleeve. There will be a
m
aximum of 6 cells per pallet.
Storage
1. Cells should be stored indoors in a clean, level, dry, cool
location. Recommended storage temperature is 0°F to 90°F
(–18°C to 32°C).
2. Stored lead-acid cells self discharge and must be
given a boost charge to prevent permanent performance
degradation.
F to 77°F (-18°C to 25°C) storage:
Batteries should be recharged six months from date
of manufacture.
>7F (25°C) storage:
Use the chart below for recharge intervals. Voltage read-
ings should be taken on a monthly basis. Cells that reach
2.10V per cell or less should be recharged regardless of
scheduled interval. Record dates and conditions for all
charges during storage.
3. If a boost charge is required; the recommended charge is
24 hours at a constant voltage equal to 2.40V per cell.
4. Do not store beyond 12 months.
5. Store in horizontal position only.
3 x 2 Module Assembly
2 x 2 Module Assembly
4