62 Part Number GA_SM 08/18
Refrigeration Section 8
Service Procedures
Always use gas detection equipment when working on
R-290 systems
Set the alarm to 15% of the LFL (Lower Flammability
Level)
Make sure all ignition sources are removed from the
work area
Maintain a 35’ area work area free of any ignition source
Flames, sparks, and static electricity can ignite leaking
refrigerant
Always reclaim and purge system (twice) before using
torch on system
Always run the unit a minimum of 5 minutes before
reclaiming refrigerant
Follow evacuation (500 microns minimum) & purging
procedures
Passive recovery
Charging with R-290
Charging with R-290 is similar to charging systems with
hydrocarbons
Like all blend refrigerants, R-290 systems must be
charged with liquid to maintain correct composition of
the blend
Be sure that the unit is grounded before charging
It is very important to take care NOT to overfill the
system
Hydrocarbon charge sizes are typically 40% to 50% less
than that of fluorocarbons