breaker, as shown in Table 3;
Table 3 Rated current and the cross-sectional area of connecting wires
Wire cross-sectional area mm²
Wiring tightening torque N .m
2.0 for power end and load end
f) This series of circuit breakers are rail-mounted, and TH35-7.5 steel mounting rails are available.
g) When the ambient temperature changes, the rated current value is corrected accordingly, and the
temperature correction coefficients are listed in Table 4;
Table 4 Rated current and temperature correction coefficient table
Corrected value of rated current A
h) When the handle moves upwards, this means that the circuit is in the ON state; when the handle moves
downwards, this means that the circuit is in the OFF state;
i) Insert the residual current operated circuit breaker into the mounting rail until it is fixed on the rail without
any looseness or falling off. To remove the residual current operated circuit breaker, push it upward
forcedly and pull its upper portion outwards until the circuit beaker is removed from the mounting rail.
Maintenance and repair:
a) The maintenance and repair of the product must be performed by qualified professionals;
b) Do not maintain or repair the live product;
c) Maintain the product once a year under normal operating conditions.The maintenance contents see Table
5.