Particulate
Contamination
Specifications
Residual dust present in the air must have a deliquescent point less than 60%
relative humidity.
NOTE: Applies to data center and non-data center environments.
Gaseous
Contamination
Specifications
Copper Coupon
Corrosion Rate
<300 Å/month per Class G1 as defined by ANSI/ISA71.04-1985.
Silver Coupon
Corrosion Rate
<200 Å/month as defined by AHSRAE TC9.9.
NOTE: Maximum corrosive contaminant levels measured at ≤50% relative humidity.
72