EasyManua.ls Logo

Delta Electronics ASDA-A2 Series - Page 221

Delta Electronics ASDA-A2 Series
583 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 7 Motion Control Functions
The Ways to Call a PR
There are 64 position settings in PR mode. PR 0 is homing mode and the others (PR 1 ~ 63)
can be user-defined. For the ways to call a PR, please refer to the table below:
Command Source Explanation
Standard
DI signals:
CTRG + POS0 ~ 5
Use DI signals, POS0 ~ 5 to specify the desired trigger
procedure number (PR), and then use the rising-edge of
DI signal, CTRG to trigger a PR.
Suitable application: PC or PLC commands the servo drive
by using DI signals
Special DI signals: STP, SHM
DI signal: Set STP from OFF to be ON, and the command
will stop.
DI signal: Set SHOM from OFF to be ON, and the servo
drive will start to perform homing operation.
Event DI signals: EV1 ~ 4
There are 4 events with rising and falling edges can be
set to trigger a specific PR.
DI signals: Trigger the command by changing the status
of EV1 ~ 4
P5-98: Event Rising-edge Trigger Command (OFF ON)
P5-99: Event Falling-edge Trigger Command (ON OFF)
Suitable application: sensor, preset trigger procedure
Software P5-07
Set P5-07 to the desired trigger procedure number (PR)
and it will trigger the dedicated position command
immediately.
P5-07 can be set through the keypad / communication
(RS-232/485 and CANopen.
Suitable application: PC or PLC commands the servo drive
by using the communication.
The number from 0 to 63 can be put into P5-07 to call a
PR respectively. PR#0 is defined as homing procedure.
The P5-07 will reply appropriate message about the result
of executing PR.
Others
Trigger the
command after
Capture operation.
Trigger the
command after E-
Cam is disengaged.
After Capture operation is completed, it will trigger PR 50.
This function is enabled by the Bit3 setting of P5-39.
After the electronic cam is disengaged, it will return to PR
mode and trigger the specified PR designated by BA
setting of P5-88.
(ASDA-A2 series L type models does not provide this
function.)
7-18 Revision January 2011
Call 1(800)985-6929 for Sales
deltaacdrives.com
sales@deltaacdrives.com
Call 1(800)985-6929 for Sales
deltaacdrives.com
sales@deltaacdrives.com

Related product manuals