Chapter 4 Parameter Settings|DD Series
4-7
Paramete
r
Explanation Settings
Factory
Setting
VF
VFP
SVC
FOC
FOC
02.09
Multi-function Output
(Relay2)
1: AC drive in operation 17
02.10
Multi-function Output
(MO1)
2: Zero speed frequency signal
(including STOP)
0
02.11
Multi-function Output
(MO2)
3: AC drive ready
0
02.12
Multi-function Output
(MO3) (Communication)
4: Low voltage warning(Lv) 0
5: Fault indication
6: Overhead warning (Pr.06.09)
7: Detection of braking resistor action
level
8: Warning indication
9: Over voltage warning
10: OD command
11: CD command
12: Demo Indication
13: Demo complete
14: Emergency stop indication
15: Force stop indication
16: Door close complete (limit) signal
output
17: Door open complete (limit) signal
output
18: Door close error
19: Position Complete Signal
20: Position Detection 1(for door close
only)
21: Position Detection 2(for door close
only)
22: Position Detection 3(for door close
only))
23: Position Detection 1(for door open
only)
24: Position Detection 2(for door open
only)
25: Position Detection 3(for door open
only)
26: PG feedback error
27: output signal when unable to open
the door
28: over torque (OT1)
02.13
Multi-function Output
Direction
0~65535 0
02.14
Position Detection Signal 1
0.0~100.0% 25.0
02.15
Position Detection Signal 2
0.0~100.0% 12.5
02.16
Position Detection Signal 3
0.0~100.0% 7.5