Chapter 4 Parameter Settings|DD Series
4-2
4-1 Summary of Parameter Settings
00 System Parameters : This parameter can be set during operation.
Paramete
r
Explanation Settings
Factory
Setting
VF
VFP
SVC
FOC
FOC
00.00
Identity Code of AC motor
drive
0: 200w
2: 400w
Read
only
00.01
Rated Current Display of
AC motor drive
0: 1.50A
2: 2.50A
Read
only
00.02
Parameter Reset
0: No function
1: Parameters locked
8: Keypad locked
10: All parameters are reset to factory
setting (33.3Hz, 230V)
0
00.03
Start-up Display Selection
0: Display the frequency command value
(F)
1: Display the actual output frequency
(H)
2: Display the content of user-defined
unit (U)
3: Display the output current (A)
0
00.04
Content of Multi Function
Display
0: Display output current (A )
1: Display actual frequency (Hz)
2: Display DC-BUS voltage ( U)
3: Display output voltage( E )
4: Display power factor angle (n.)
5: Display output power (kW)
6: Display motor angle speed (HU)
7: Display the drive’s estimated output
torque (kg-m)
8: Display PG pulse input position
9: Display the electrical angle
10: Display IGBT temperature(oC)
11: Display digital input ON/OFF status
12: Display digital output ON/OFF status
13: Display current multi-step speed
14: Display the corresponding CPU pin
status of digital input
15: Display the corresponding CPU pin
status of digital input 16:Actual
output voltage when malfunction
17: Actual DC-BUS voltage when
malfunction
18: Actual output frequency when
malfunction
19: Actual output current when
malfunction
20: Actual frequency command when
malfunction
21: Door width in % or step speed
22: Door width(pulse)
23: Over modulation indication
2