Chapter 4 Parameter Settings|DD Series
4-3
Paramete
r
Explanation Settings
Factory
Setting
VF
VFP
SVC
FOC
FOC
00.05
Software version
Read only(Different versions will display
differently)
#.##
00.06
Password Input
0~9999
0~2:times of wrong password
0
00.07
Password Set
0~9999
0: No password set or successful input in
Pr.00-06
1: Password has been set
0
00.08
Control Method
0: V/f control
1: V/f Control + Encoder (VFPG)
2: Sensorless vector control (SVC)
3: FOC vector control + Encoder
(FOCPG)
8: FOC PM control (FOCPM)
0
00.09
Door Control Mode
0: Distance control mode
1: Reserved
2: Multi-step speed control mode
3: Speed control mode
3
00.10
Output Direction
0: Runs in same direction as setting
1: Runs in different direction than setting
0
00.11
Carrier Frequency
Selection
02~15 kHz
02~10kHz (for VFDXXXDDXXE model
only)
10
00.12
Auto Voltage Regulation
(AVR) Function
0: Enable AVR
1: Disable AVR
2: Disable AVR when deceleration stop
0
00.13
Source of the Master
Frequency Command
0: by digital keypad input
1: by external terminal
2: by RS-485 serial communication
1
00.14
Demo Mode
0: Disable
1: Display demo action
0
00.15
Frequency Testing
Command
0~120.00 Hz 0