01 Motor Parameters : This parameter can be set during operation.
Paramete
r
Explanation Settings
Factory
Setting
VF
VFP
SVC
FOC
FOC
01.00
Motor Auto Tuning (PM)
0: No function
1: Auto-tuning for PM motor parameters
(brake locked)
2: Auto-tuning for PG offset angle without
load (Pr.01.09)
3: Auto-tuning for PG offset angle with
load (Pr.01.09)
0
01.01
Full-load Current of motor
(PM)
(20~120%)*00.01 Amps 1.00
01.02
Rated power of Motor (PM)
0.00~655.35kW 0.06
01.03
Rated speed of Motor (rpm)
(PM)
0~65535 250
01.04
Number of Motor Poles
(PM)
2~96 16
01.05
Rs of Motor parameter
(PM)
0.0~655.35Ω
13.900
01.06
Ld of Motor Parameter
(PM)
0.0~6553.5mH 169.4
01.07
Lq of Motor Parameter
(PM)
0.0~6553.5mH 169.4
01.08
Back Electromotive Force
(PM)
0.0~6553.5Vrms 0.0
01.09
Angle between Magnetic
Pole and PG Origin (PM)
0.0~360.0° 360.0
01.10
Magnetic Pole
Re-orientation (PM)
0:No function
1:Reset magnetic pole position
0
01.11
Motor Auto Tuning (IM)
0: No function
1: Rolling test
2: Static test
3: Reserved
0
01.12
Full-load Current of Motor
(IM)
(20~120%)*00.01 Amps 1.00
01.13
Rated power of Motor (IM)
0.00~655.35kW 0.06
01.14
Rated speed of Motor (rpm)
(IM)
0~65535 250
01.15
Number of Motor Poles (IM)
2~48 16
01.16
No-load Current of Motor
(IM)
00~ Pr.01.12 factory setting #.##
01.17
Rs of Motor (IM)
0.000~65.535Ω
0.000
01.18
Rr of Motor (IM)
0.000~65.535Ω
0.000
01.19
Lm of Motor (IM)
0.0~6553.5mH 0.0
01.20
Lx of Motor (IM)
0.0~6553.5mH 0.0
01.21
Torque Compensation Time
Constant