EasyManua.ls Logo

Delta Electronics VFD-DD Series - Page 57

Delta Electronics VFD-DD Series
141 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 4 Parameter Settings|DD Series
4-33
Magnetic Pole Re-orientation (PM)
Control mode
FOCPM
Factory setting: 0
Settings
0:No function
1:Reset magnetic pole position
This function is used to search magnetic pole position and is only available on permanent magnet motor.
When encoder origin-adjustment function (Pr.01-09= 360.0) is not available, the motor operation efficiency
can only achieve up to 86% of its best efficiency. In this case, if user needs to improve the operation
efficiency, reapply power or set Pr.01-10=1 to measure magnetic pole position again.
Motor Auto Tuning (IM)
Control mode
SVC FOCPG
Factory setting: 0
Settings
0: No function
1: Rolling test
2: Static test
3: Reserved
Set Pr.01-11 to 1 or 2, Press Runto begin auto tuning. The measured value will be written into Pr.1-17
to Pr.01-20 (Rs, Rr, Lm, Lx, no-load current).
AUTO-Tuning Process (rolling test):
1. Make sure that all the parameters are set to factory settings and the motor wiring is correct.
2. Make sure the motor has no-load before executing auto-tuning and the shaft is not connected to any
belt or gear motor. It is recommended to perform auto-tuning in static test if the motor can’t separate
from the load.
3.
Pr. of Motor
Motor Rated
Frequency
01-32
Motor Rated
Voltage
01-33
Motor Full-load
Current
01-12
Motor Rated
Power
01-13
Motor Rated
Speed
01-14
Motor Pole
Numbers
01-15
4. Set Pr.01-11=1 and pressRun, the drive will begin auto-tuning. Please be aware of the motor that
it starts spinning asRun is pressed.
5. When auto-tuning is completed, please check if the measured values are written into Pr.01-16
~01-20).
6. Mechanical equivalent circuit
V
S
I
Rs
Rr
Lx
Lm
Pr.01-17
Pr.01-20
Pr.01-19
Pr.01-18
When Pr.01-11 is set to 2 (static test), user needs to write no-load current value of motor into
Pr.01-16.