EasyManua.ls Logo

Delta Electronics VFD-DD Series - Page 92

Delta Electronics VFD-DD Series
141 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 4 Parameter Settings|DD Series
4-68
11-bit character frame (For RTU):
Start
bit
0123456
Stop
bit
Stop
bit
8-bit character
11-bit character frame
( 8.N.2 )
Start
bit
01234
5
6
Even
parity
Stop
bit
11-bit character frame
( 8.E.1 )
Start
bit
01234
5
6
Stop
bit
11-bit character frame
( 8.O.1 )
Odd
parity
7
7
7
8-bit character
8-bit character
3.1 Communication Protocol
Communication Data Frame:
ASCII mode:
STX Start character ‘: (3AH)
Address Hi
Address Lo
Communication address:
8-bit address consists of 2 ASCII codes
Function Hi
Function Lo
Command code:
8-bit command consists of 2 ASCII codes
DATA (n-1)
…….
DATA 0
Contents of data:
Nx8-bit data consist of 2n ASCII codes
n<=16, maximum of 32 ASCII codes
LRC CHK Hi
LRC CHK Lo
LRC check sum:
8-bit check sum consists of 2 ASCII codes
END Hi
END Lo
End characters:
END1= CR (0DH), END0= LF(0AH)
RTU mode:
START A silent interval of more than 10 ms
Address Communication address: 8-bit address
Function Command code: 8-bit command
DATA (n-1)
…….
DATA 0
Contents of data:
n×8-bit data, n<=16
CRC CHK Low
CRC CHK High
CRC check sum:
16-bit check sum consists of 2 8-bit characters
END A silent interval of more than 10 ms