AS Series Module Manual
4- 6
_4
4.2.3 Arrangement of Terminals
AS04DA-A
D A
VO1
VO2
AG
SLD
AG
VO4
0V
24V
SLD
SLD
AG
IO3
AG
SLD
IO1
IO4
IO2
04DA
PWR
ERR
VO3
4.2.4 Control Registers
*If you use HWCONFIG to set values in CRs, once the set value is downloaded, the values can be retained in
the module; however if you use TO instruction to write data into CRs, the values CANNOT be retained, after
power failure or after transition of the CPU from STOP to RUN.
Note: The attribute of the CR must be W (write) to use TO instruction.
CR# Name Description
Atr. Defaults
0
Format Setup
0: integer format
1: floating-point format
R 0
1
Channel 1 mode setup
0: closed
1: -10 V to +10 V (default)
2: 0 V10 V
3: -5 V to +5 V
4: 0 V5 V
5: 1 V5 V
6: 0 mA20 mA
7: 4 mA20 mA
R/W
1
2
Channel 2 mode setup
R/W
3
Channel 3 mode setup
R/W
4
Channel 4 mode setup
R/W
5
Channel 1 offset
Range: -32768 to +32767
R/W 0