C.1 EMC Standards for an AS Series System
C.1.1 AS Series System EMC Standards
The EMC standards that are applicable to an AS series system are listed in the following tables.
EMI
Port Frequency range Level (Normative) Reference standard
Enclosure port
(radiated)
(measured at a
distance of 10 meters)
30-230 MHz 40 dB (μV/m) quasi-peak
IEC 61000-6-4
230-1000 MHz 47 dB (μV/m) quasi-peak
AC power port
(conducted)
0.15-0.5 MHz
79 dB (μV) quasi-peak
IEC 61000-6-4
66 dB (μV) average
0.5-30 MHz
73 dB (μV) quasi-peak
60 dB (μV) average
EMS
Environmental
phenomenon
Reference
standard
Test Test level
Electrostatic
discharge
IEC 61000-4-2
Contact ± 4 kV
Air ± 8 kV
Radio frequency
electromagnetic field
Amplitude modulated
IEC 61000-4-3
80% AM,
1 kHz sinusoidal
2.0-2.7 GHz 1 V/m
1.4-2.0 GHz 3 V/m
80-1000 MHz 10 V/m
Power frequency
magnetic field
IEC 61000-4-8
60 Hz 30 A/m
50 Hz 30 A/m
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta AS164P-A and is the answer not in the manual?

Delta AS164P-A Specifications

General IconGeneral
BrandDelta
ModelAS164P-A
CategoryNetwork Hardware
LanguageEnglish

Related product manuals