Chapter 1 Overview of Parallel Control Parallel Control Solution
6
C2000-R
Rated Output Capacity (kVA)
Applicable Motor Output (kW)
Applicable Motor Output (HP)
120% of rated output current: 1 minute for every 5 minutes
Max. Output Frequency (Hz)
Rated Output Capacity (kVA)
Applicable Motor Output (kW)
Applicable Motor Output (HP)
1.0 Hz Operation
80% of rated output current: continuous operation
150% of rated output current: 5 seconds for every 10 minutes
2.1 Hz to Max. Operation Frequency
150% of rated output current: 1 minute for every 5 minutes
180% of rated output current: 3 sec. for every 30 seconds
Max. Output Frequency (Hz)
Rated Voltage / Frequency
3-phase AC 380–480V (-15 – +10%), 50 / 60 Hz
Displacement Power Factor (cosθ)
NOTE:
1. The carrier frequency is default. Increasing the carrier frequency requires a reduction in current. Refer to
Section 9-4 Derating Curve in C2000-R User Manual.
2. The AC motor drive should operate in derating current when its control method is set to FOC Sensorless,
TQC+PG, TQC sensorless. PM+PG or PM sensorless. Refer to Pr.06-55 for more information.
3. Select the AC motor drive with capacity one grade larger for the impact load application.
4. The rated input current will be affected by not only power transformer and the connection of the reactors on
input side, but also fluctuates with the impedance of power side.