Details the DAC-606 controller, its BACnet compatibility, and I/O capabilities for various applications.
ORCAview OWS and controller firmware must match versions, with an exception for UL 864 models.
Lists the DAC-606 (Rev. 3.2) and its installation guide.
Lists supporting documentation like wiring guidelines, operator guides, and release notes.
Specifies power-limited circuits, approved transformers, and Class 2 power supplies for UL 864 installations.
Highlights ESD sensitivity, requiring ground straps, and CE conformance transformer requirements.
Describes mounting the controller using screws in an appropriate location or enclosure that meets code requirements.
Provides a table with physical dimensions (A-G) in millimeters for the controller enclosure.
Identifies key components and ports on the DAC-606 board, including power, network, inputs, and outputs.
Explains Derived Network Addressing (DNA jumper) and Controller Addressing via DIP switches for BACnet setup.
States wiring must conform to NEC/local codes, use Class 2 transformers, and avoid autotransformers.
Warns about potential hazards like multiple disconnect switches and interconnected power supplies.
Specifies a 24 VAC Class 2 power supply, 18-16 AWG wire, and conditions for powering multiple devices.
Details proper grounding procedures for the controller using the ground lug for safety and RS-485 communication.
Outlines requirements for reliable MS/TP communication, including cable type, impedance, daisy-chain wiring, and repeaters.
Explains how to configure inputs for 4-20mA, 10KΩ Thermistor, 5V, or 10V signals using jumpers.
Describes selecting internal or external power sources for binary triac outputs and notes triac limitations for 24 VAC switching.
Details the function and status indication of Power, Scan, Network (NET1/NET2), and Output LEDs on the controller board.
Lists power requirements, ambient ratings, and communication port specifications.
Details input/output types, binary triac output specs, processor, memory, and listings.
Provides manufacturer name, address, product name, and model numbers.
Lists product conformance to EN standards for emissions and immunity requirements for industrial/residential environments.
States compliance with EMC Directive and testing in a typical configuration.
Provides FCC and IC compliance statements for Class digital devices, covering interference and regulations.
Lists UL requirements met by the product, including Energy Management Equipment and Fire Alarm Systems accessories.