Delta Controls
Page 10 of 12
Product Specifications
Power Requirements
24 VAC, Class 2, 60Hz
Power Consumption
8 VA
80 VA max (with fully loaded Binary Outputs (Triacs))
Ambient Ratings
32° to 131°F (0° to 55°C), 10 to 90% RH (non condensing)
Communication Ports
NET1
BACnet MS/TP (RS-485)
Communication: 9600, 19200, 38400, 76800 bps (Default)
Maximum of 99 controllers
NET2
LINKnet
Communication: 76800 bps
Maximum of 6 LINKnet controllers including up to two DFM
controllers
Service
Port
RJ-11 Jack
Used with Delta Controls service tool devices (for example,
CON-768)
Inputs
6 Universal Inputs (10 bit), jumper configurable for the following input
types:
0-5 VDC
0-10 VDC
10 K Thermistor
Dry Contact (using 10 K Thermistor jumper setting
4-20 mA
Outputs
6 Binary Triac Outputs c/w LED status indication
Switching 24VAC@0.5 Amp maximum per output
Leakage Current per Triac is 160 µA
Technology
32 bit processor
1 MB (8 megabit) Flash Memory
256 KB SRAM memory
Listings
UL 916 Listed
BTL Listed
UL 864 Listed (DAC-606-UL864 model only)
Compliance
CE
FCC

Related product manuals