Model Name Outline Function Explanation
Terminal layout
V0+
I0+
V1+
I1+
COM
0~+10V
0~+10V
CH0
CH1
Voltage output
Load Impedance:
Output voltage 1KΩ
Output current 500Ω
V0+
I0+
V1+
I1+
COM
CH0
CH1
0~20mA
0~20mA
Current output
output load: 0~500Ω
Item Voltage output Current output
Analog signal DC 0~+10V DC 0~20mA
Output impedance
0.5
Ω
1M
Ω
Resolution (12bit) 2.5mV (10/4000) 5uA (20/4000)
Update time for conversion
D1118 setting (
K
5, unit: ms)
Digital value input D1116 (CH0) D1117 (CH1)
Characteristic curve
4000
10V
0
voltage
output
digital input
digital input
0
20mA
4000
cur rent
out put
User can move v
alue to D1116 (CH0) or D1117 (CH1) to get correspondent
output voltage by using instruction MOV.
DVP-F232S
(RS-232 card)
When two built-in COM1 (RS-232) and COM2 (RS-
485) are not enough for
use, you can add one COM by this card (number is 3 and is called COM3.
There are two interfaces, RS-232 and RS-485, for you to use. Its general
function is the same as COM1 but communication baud rate is
9600/19200/38400 bps. PLC scan time will be added at least 0.8ms ~ 2ms
due to COM3.
Usage limit: PC1 and PC2 can’t execute ladder diagram monitor function
simultaneously when COM2 is slave mode and connect to PC1 with
executing WPLSoft/ISPSoft and COM3 also connects to PC2 with
executing WPLSoft/ISPSoft. But other communication function is normal.
COM1 is out of this limit.
Master
PC 2
HMI
PC
PC 1
HMI
COM1
COM2
COM3
(RS-232)
(RS-485)
DVP-F232S or DVP-F485S/F485
DVP EH MP U
AC drive or Servo
Extension card for
communication port
select one Master device
or
Terminal Layout (DB-9
female)
GND
Tx
Rx
5
3
2
1
9
8
7
6
4
NC
NC
NC
NC
NC
NC
Note:
Please pay attention to
signal of pin2 and pin3
when this communication
port is connected to PC or
HMI. Especial that this
definition is different from
DVP-F232 card.
DVP-F485S
(RS-485 card)
D+
D-
D+: signal
(+)
D-: signal (-)