DVP-ES2/EX2/EC5/SS2/SA2/SX2/SE&TP Operation Manual - Programming 
 
Step1:   
Set K
I
 and K
D
 as 0, and K
P
 as 5, 10, 20, 40. Record the SV and PV respectively and the results are 
as the figure below. 
1.5
1
0.5
0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
K  =40
P
K  =20
P
K  =10
P
SV=1
K  =5
P
Time (sec)
 
 
Step 2: 
When K
P 
is 40, response overshoot occurs, so we will not select it.   
When K
P
 is 20, PV response is close to SV and won’t overshoot, but transient MV will be to large 
due to a fast start-up. We can put it aside and observe if there are better curves. 
When K
P
 is 10, PV response is close to SV and is smooth. We can consider using it. 
When K
P
 is 5, the response is too slow. So we won’t use it. 
 
Step 3:   
Select K
P
 = 10 and increase K
I
 gradually, e.g. 1, 2, 4, 8. K
I
 should not be bigger than K
P
. Then, 
increase K
D
 as well, e.g. 0.01, 0.05, 0.1, 0.2. K
D
 should not exceed 10% of K
P
. Finally we obtain 
the figure of PV and SV below. 
1.5
1
0.5
0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
PV=SV
K  =10,K  =8,K  =0.2
P I D
Time (sec)
 
Note: The example is only for reference. Users have to adjust parameters according to the 
condition of the actual control system.