Warning
EN
DVP04AD-S/DVP04AD-S2 is an OPEN-TYPE device. It should be installed in a control cabinet free of airborne dust, humidity, electric shock
and vibration. To prevent non-maintenance staff from operating DVP04AD-S/DVP04AD-S2, or to prevent an accident from damaging
DVP04AD-S/DVP04AD-S2, the control cabinet in which DVP04AD-S/DVP04AD-S2 is installed should be equipped with a safeguard. For
example, the control cabinet in which DVP04AD-S/DVP04AD-S2 is installed can be unlocked with a special tool or key.
EN
DO NOT connect AC power to any of I/O terminals, otherwise serious damage may occur. Please check all wiring again before
DVP04AD-S/DVP04AD-S2 is powered up. After DVP04AD-S/DVP04AD-S2 is disconnected, Do NOT touch any terminals in a minute. Make
sure that the ground terminal
on DVP04AD-S/DVP04AD-S2 is correctly grounded in order to prevent electromagnetic interference.
FR
DVP04AD-S/DVP04AD-S2 est un module OUVERT. Il doit être installé que dans une enceinte protectrice (boitier, armoire, etc.) saine,
dépourvue de poussière, d’humidité, de vibrations et hors d’atteinte des chocs électriques. La protection doit éviter que les personnes non
habilitées à la maintenance puissent accéder à l’appareil (par exemple, une clé ou un outil doivent être nécessaire pour ouvrir a protection).
FR
Ne pas appliquer la tension secteur sur les bornes d’entrées/Sorties, ou l’appareil DVP04AD-S/DVP04AD-S2 pourra être endommagé. Merci
de vérifier encore une fois le câblage avant la mise sous tension du DVP04AD-S/DVP04AD-S2. Lors de la déconnection de l’appareil, ne pas
toucher les connecteurs dans la minute suivante. Vérifier que la terre est bien reliée au connecteur de terre afin d’éviter toute
interférence électromagnétique.
Introduction
Model Explanation & Peripherals
Thank you for choosing the Delta DVP series PLC. The analog input module DVP04AD-S/DVP04AD-S2 receives external 4-point
analog signal input (voltage or current) and converts it into 14-bit digital signals. A DVP series slim type PLC can read data from
DVP04AD-S/DVP04AD-S2 or write data to DVP04AD-S/DVP04AD-S2 by means of the instruction FROM/TO. There are 49 CRs
(control registers) in the module, and each register has 16 bits.
Users can select input from voltage or current via wiring. Voltage input range is ±10VDC (resolution is 1.25mV). Current input range
is ±20mA (resolution is 5μA).
Product Profile & Outline
90.00
4.00
3.00
25.20
1
2
3
4
60.0
5
6
7
8
9
3
10
●
FG
V+
I+
COM
C
H
1
FG
V+
I+
COM
C
H
2
FG
V+
I+
COM
C
H
3
FG
V+
I+
COM
C
H
4
11
12
13
3.4
90.00
60.0
3.00
14
●
Unit: mm Figure 1
1. POWER, RUN and ERROR indicators 8. Extension port
2. Model name 9. Extension unit clip
3. DIN rail clip 10. DIN rail groove (35mm)
4. I/O terminals 11. RS-485 communication port
5. I/O point indicators 12. Mounting groove of the extension unit
6. Mounting hole of the expansion unit 13. DC power input
7. Nameplate 14. Extension port
External Wiring
DVP04AD-S
Arrangement of the
terminals
-10V~+10V
V+
I+
COM
CH1
-20mA~+20mA
V+
I+
COM
CH4
*5
*2
24V
0V
DC24V
+15V
-15V
AG
*4
FG
FG
*3
CH1
104.7K
100K
250
CH4
104.7K
100K
AG
AG
250
Shielded
cable*1
Voltage input
Shielded
cable*1
Current input
Connected to on
a power supply module
DC/DC
converter
System ground
Ground (Impedance: Less than 100 )
V+
I+
COM
FG
V+
.
.
I+
COM
FG
V+
I+
COM
FG
I+
COM
FG
V+
ENGLISH