Chapter 5 CPU and Module Devices
5-29
Adjusted Offset Value, Adjusted Gain Value:
Note 1: When using Mode 6 for input or Mode 2 for output, the channel do NOT provide setups for adjusted Offset and
Gain value.
Note 2: When mode changes, the adjusted Offset and Gain value returns to defaults.
40 O R/W Set value changing prohibited Prohibit set value changing in CH1 ~ CH4 Default= H’0000.
Save all the set values, Default =H’0000
43 X R Error status
Register for storing all error status. Refer to table of error status for
more information.
100 O R/W Enable/Disable limit detection
Upper and lower bound detection, b0~b5 corresponds to
CH1~CH6 (0: Disable/ 1: Enable). Default= H’0000.
101 X R/W Upper and lower bound status
Display the upper and lower bound status. (0: Not exceed /1:
Exceeds upper or lower bound value), b0~b5 corresponds to
Ch1~Ch6 for lower bound detection result; b8~b13 corresponds to
CH1~CH6 for upper bound detection result.
Set value of CH1 upper bound
Set value of CH1~CH6 upper bound. Default = K32000.
Set value of CH2 upper bound
Set value of CH3 upper bound
Set value of CH4 upper bound
Set value of CH5 upper bound
107 O R/W Set value of CH6 upper bound
Set value of CH1 lower bound
Set value of CH1~CH6 lower bound. Default = K-32000.
Set value of CH2 lower bound
Set value of CH3 lower bound
Set value of CH4 lower bound
Set value of CH5 lower bound
Set value of CH6 lower bound
Output update time of CH5
Set output update time of CH5 ~ CH6
Output update time of CH6
118 O R/W
LV output mode setting of Ch5 ~
Ch6
Set the output mode of CH5~CH6 when the power is at LV (low
voltage) condition. Default=0
Symbols:
O: When CR#41 is set to H’5678, the set value of CR will be saved.
X: Set value will not be saved.
R: You can use FROM instruction to read data.
W: You can use TO instruction to write data.
※ CR#0 for module reset
You can use CR#0 to reset all the settings by simply writing H’4352 in CR#0 and wait for one second before turning the
power OFF and then ON again, all the modules connected will be initialized. It is suggested to connect to only one module
for module reset. And this is only available for firmware V1.14 or later.
※ CR#43: Error status value. See the table below:
bit0 K1 (H’1) Power supply error bit6 K64 (H’40) CH4 Conversion error
bit1 K2 (H’2) Hardware error bit9 K512 (H’0200) Mode setting error
bit2 K4 (H’4) Upper/lower bound error bit10 K1024 (H’0400) Sampling range error
bit3 K8 (H’8) CH1 Conversion error bit11 K2048 (H’0800)
Upper / lower bound setting
Set value changing prohibited