Chapter 5 CPU and Module Devices
5-31
5_
Mode 0 of CR#2 ~ CR#5
-10V ~ +10V, Default: Gain = 16,000= , Offset = 0
Mode 1 of CR#2 ~ CR#5
-5V ~ +5V, Default: Gain = 16,000= , Offset = 0
Range of digital conversion
-32,000 ~ +32,000
Max./Min. range of digital
conversion
-32,384 ~ +32,384
Mode 0:
Mode 1:
Digital input
10V
5V
-5V
+32000
-10V
-32000
+16000
0
Gain
Offset
Voltage
output
-32768
+32
Voltage input
+32000
+16000
-16000
5V
-32000
-5V
2.5V
0
Gain
Offset
Digital
output
+32384
-32384
Mode 2 of CR#2 ~ CR#5
0V ~ +10V, Default: Gain = 16,000= ), Offset = 0
Mode 3 of CR#2 ~ CR#5
0V ~ +5V, Default: Gain = 16,000= ), Offset = 0
Range of digital conversion
0 ~ +32,000
Max./Min. range of digital
conversion
-384 ~ +32,384
Mode 2:
Mode 3:
Voltage input
+32000
+16000
10V
5V
0
Gain
Offset
Digital
output
+32384
-384
Voltage input
+32000
+16000
5V
2.5V
0
Gain
Offset
Digital
output
+32384
-384
Mode 4 of CR#2 ~ CR#5
-20mA ~ +20mA, Default: Gain = 16,000= , Offset = 0
Range of digital conversion
-32,000 ~ +32,000
Max./Min. range of digital
conversion
-32,384 ~ +32,384