Volta
g
e Protection
Fre
q
.
Protection
Re
connect T 300s
P Ram
p
U
p
6000%/m
Hi
g
h Off 64.05Hz
Hi
g
h On 63.00Hz
Hi
g
h Off T 0.1S
Low Off 55.95Hz
Low On 57.00Hz
Low Off T 0.1S
Hi Off Slow 63.05Hz
Hi On Slow 63.00Hz
Hi Off Sl T 20.5S
Lo Off Slow 56.95Hz
Lo On Slow 57.00Hz
Lo Off Sl T 20.5S
EXIT
ENT
►
Trip value of OFR2
Hysteresis frequency of OFR2
Trip time of OFR2
Trip value of UFR2
Hysteresis frequency of UFR2
Trip time of UFR2
Trip value of OFR1
Hysteresis frequency of OFR1
Trip time of OFR1
Trip value of UFR1
Hysteresis frequency of UVR1
Trip time of UVR1
Figure B-1: Procedure to confirm Grid Code via LCD – HECO A shown
Figure B-2: Details of HECO A: L/H FRT via LCD Settings menu
Meter
Ener
gy
Lo
g
Event Lo
g
Inverter Info
.
►
S/N:O2X16100005W0
Install:01/01/2016
INV ID: 1
FW Version
DSP: 118 RED: 104
CO
M: 102 ARC: 101
SCM: 104
AC Connection: 3P4W
Max
.
Power: 83000W
D
ry cont A: Disable
Dry cont B: Disable
Country:
HE
CO A
Insulation:
100k
Baud Rate:
19200bps
EPO: Normal Open
Grid Settin
g
s
Active Pwr Settin
g
s
React Pwr Settin
g
s
EXIT
ENT
►
Appendix B: HECO
121