Chapter 5 Methods of Anomaly Diagnosis |V FD-VJ- 
 
 
5-4
No.  Display Code 
Fault 
Description 
Troubleshooting 
Fault codes 
defined by 
Delta  
(2021H 
Low Byte) 
CANopen 
Fault 
Register 
(1001H 
 bit 0~7) 
DS402 
Fault  
Codes 
(603FH) 
E5 
occ 
 
IGBT short 
circuit between 
upper and lower 
bridge. (occ) 
Short-circuit is detected between the 
upper and lower bridge of the IGBT 
module. Check the motor wiring. Cycle 
the power, if occ still exists, return to the 
factory for repair. 
0005H 2 2250H 
E6 
ocS 
 
Over-current or 
hardware failure 
in current 
detection at 
Stop. (ocs) 
Send back to manufacturer for repair. 
0006H
 
1
 
2214H
 
E7 
ovA 
 
DC BUS 
over-voltage 
during 
acceleration. 
(ovA) 
230V: DC 415V 
460V: DC 830V 
 
1.  Check if the input voltage is within the 
range of voltage rating of Hybrid 
Servo Drive and monitor for any 
occurrence of surge voltage. 
 
2.    The issue can be resolved by 
adjusting the software brake action 
level in Pr.02-00. 
 
3.    When such error occurred at the 
beginning, during or at the end of the 
pressure/ flow command, adjust 
Pr00-29 ~Pr0032 <Ramp up/down 
rate of pressure/ flow command> or 
Pr00-46 ~Pr00-49 <Pressure/ flow 
reference S1/S2 time> 
 
0007H  2  3210H 
E8 
ovd 
 
DC BUS 
over-voltage 
during 
deceleration.(ov
d) 
0008H  2  3210H 
E9 
ovn 
 
DC BUS 
over-voltage at 
constant speed. 
(ovn) 
009H  2  3210H 
E10 
ovS 
 
Over voltage 
occurs at stop 
and hardware 
failure. (ovS) 
Check if the input voltage is within the 
range of voltage rating of hybrid servo 
drive and monitor for any occurrence of 
surge voltage. 
000AH
 
2
 
3210H
 
E11 
LvA 
 
DC bus voltage 
is lower than the 
setting at 
Pr02-07 during 
acceleration. 
(LvA) 
1.    Check if the voltage of input power is 
normal. 
 
2.    Check if there is any sudden heavy 
load. 
 
3.    Adjust the low voltage level in 
Pr02-07. 
 
000BH
 
2
 
3220H