EasyManua.ls Logo

Delta VFD-VJ Series - Page 44

Delta VFD-VJ Series
235 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 2. Wiring | VFD-VJ
2-19
VJ-C Air Cooled
Frame E4
Main Circuit Terminals:
R/L1, S/L2, T/L3, U/T1, V/T2, W/T3, DC+, DC-, B1, B2
Grounding Terminal:
Models
Max. Wire
Gauge
Mini. Wire
Gauge
Screw Size and
Torque Force
(± 10%)
Max. Wire
Gauge
Mini. Wire
Gauge
Screw Size
and
Torque Force
(± 10%)
VFD300VL23C-J
120mm
2
(4/0 AWG)
70 mm
2
(2/0 AWG)
M8
180 kg-cm
(156.2 lb-in)
(17.65 Nm)
70 mm
2
(2/0 AWG)
35 mm
2
(2 AWG)
M8
180 kg-cm
(156.2 lb-in.)
(17.65 Nm)
VFD370VL23C-J
120mm
2
(4/0AWG)
120 mm
2
(4/0 AWG)
70 mm
2
(2/0 AWG)
VFD450VL43C-J
50 mm
2
(1/0 AWG)
50 mm
2
(1/0 AWG)
25 mm
2
(4 AWG)
VFD550VL43C-J
70 mm
2
(2/0 AWG)
70 mm
2
(2/0 AWG)
35 mm
2
(2 AWG)
VFD750VL43C-J
120 mm
2
(4/0 AWG)
120 mm
2
(4/0 AWG)
70 mm
2
(2/0 AWG)
NOTE:
1. If you install at Ta 45°C environment, select copper wire with voltage rating of 600 V and temperature
resistance of 75°C or 90°C
2. If you install at Ta 45°C above environment, select copper wire with voltage rating of 600 V and temperature
resistance of 90°C or above.
3. For UL installation compliance, use copper wires when installing. The wire gauge is based on a temperature
resistance of 75°C, in accordance with UL requirements and recommendations.
4. Do not reduce the wire gauge when using higher temperature wire.

Table of Contents

Related product manuals