Chapter 4 Parameters
VFD-EL-W 
4-74 
 
  The diagram below shows the sequential relationship between the preheating function and enabled DC brake. 
 
 
08.23 
Fire Mode 
  Settings  0: No function 
1: Forward running 
2: Running in reverse 
Default: 0
  Use this parameter with Pr.04.06–Pr.04.08 multi-function input terminals #27 or #28 (Fire mode enabled 
with/without operation command) and Pr.03.00 multi-function output terminal #25 (Fire Mode Indication). 
0: The fire mode is invalid. 
1: The motor runs in a clockwise direction (U, V, W) during fire accident. 
2: The motor runs in a counterclockwise direction (U, V, W) during fire accident. 
 
08.24 
Operating Frequency during Fire Mode 
  Settings  0.00–400.00 Hz  Default: 60.00
  Sets the AC motor drive’s operating frequency when the fire mode is enabled.  
 
08.25 
Number of Fire Mode Actions 
  Settings  Read only  Default: Read only
  As long as the fire mode is enabled for more than four minutes, regardless of whether the AC motor drive 
runs or not, the fire mode action and its number of occurrences are recorded. Note that this parameter is 
read-only. Any parameter value that is not zero voids the warranty. 
※
 
Fire mode end process flow:
 
  If you set the Pr.04.06–Pr.04.08 multi-function input terminal=27/28 to ON or the communication address to 
2002H with bit5=1 (fire mode enabled), and the fire mode is enabled for more than four minutes, and then you 
set the Pr.04.06–Pr.04.08 multi-function input terminal=27/28 to OFF or the communication address to 2002H 
with bit5=0 (no function), the counter starts to count from four minutes after the fire mode is enabled. After the 
fire mode is enabled for 2.5 hours, the AC motor drive resumes normal operation, and stops or operates to 
normal operating frequency according to the original input status. 
  If you set the Pr.04.06–Pr.04.08 multi-function input terminal=27/28 to ON or the communication address to 
2002H with bit5=1 (fire mode enabled), and the fire mode is enabled for less than four minutes, the AC motor 
drive resumes normal operation once the fire mode is disabled, and stops or operates to normal operating 
frequency according to the original input status.