Chapter 4 Parameters
VFD-EL-W 
4-24 
 
Frequency Hold 
Applications  Purpose  Functions 
Related 
Parameters 
General application 
Acceleration / 
deceleration pause 
Hold output frequency during acceleration 
/ deceleration 
04.06–04.08 
 
Auto-restart after Fault 
Applications  Purpose  Functions 
Related 
Parameters 
pumps 
For continuous and 
reliable operation 
The AC motor drive can automatically 
restart / reset up to 10 times after a fault 
occurs. 
08.15, 08.16 
 
Emergency Stop by DC Brake 
Applications  Purpose  Functions 
Related 
Parameters 
High-speed rotors 
Emergency stop without 
brake resistor 
The AC motor drive can use the DC 
brake for emergency stop when a quick 
stop is needed without a brake resistor. 
Take motor cooling into consideration 
when using DC braking often. 
08.00–08.03 
 
Over-torque Setting 
Applications  Purpose  Functions 
Related 
Parameters 
Pumps, fans and 
extruders 
To protect machines and 
for continuous / reliable 
operation 
Set the over-torque detection level. 
When OC stall, OV stall or over-torque 
occurs, the drive automatically adjusts 
the output frequency. It is suitable for 
machines like fans and pumps that 
require continuous operation. 
06.00–06.05 
 
Upper / Lower Limit Frequency 
Applications  Purpose  Functions 
Related 
Parameters 
Pumps and fans 
Control the motor speed 
within upper / lower limit 
When you cannot provide the upper / 
lower limit, gain or bias from external 
signals, you can set the limits in the AC 
motor drive. 
01.07 
01.08 
 
Skip Frequency Setting 
Applications  Purpose  Functions 
Related 
Parameters 
Pumps and fans 
To prevent machine 
resonance vibration 
The AC motor drive does not run at 
constant speed in the skip frequency 
range. You can set up to three skip 
frequency ranges. 
08.09–08.14 
 
Carrier Frequency Setting 
Applications  Purpose  Functions 
Related 
Parameters 
General application  Reduce noise 
Increase the carrier frequency to reduce 
motor noise. 
02.03