Chapter 4 Parameters
VFD-EL-W 
4-14 
 
Group 6 Protection Parameters 
Parameter
Function  Setting  Default
Customer
06.00 
Over-Voltage Stall 
Prevention 
230V series: 330.0–410.0 V  390.0   
460V series: 660.0–820.0 V  780.0 
06.01
Over-Current Stall 
Prevention during 
Acceleration 
0:Disable 
20–250% 
170 
 
06.02
Over-Current Stall 
Prevention during 
Operation 
0:Disable 
20–250% 
170 
 
06.03 
Over-Torque Detection 
Mode (oL2) 
0: Over-torque detection disabled 
0 
 
1: Over-torque detection enabled during constant 
speed operation. After over-torque is detected, 
keep running until oL1 or oL occurs. 
2: Over-torque detection enabled during constant 
speed operation. After over-torque is detected, 
stop running. 
3: Over-torque detection enabled during 
acceleration. After over-torque is detected, keep 
running until oL1 occurs. 
 
4: Over-torque detection enabled during 
acceleration. After over-torque is detected, stop 
running. 
 
06.04
Over-Torque Detection 
Level 
10–200%  150 
 
06.05 
Over-Torque Detection 
Time 
0.1–60.0 sec.  0.1 
 
06.06 
Electronic Thermal 
Overload 
(oL1) 
0: Standard motor (self-cooled by fan) 
2 
 
1: Special motor (forced external cooling) 
2: Disabled 
06.07 
Electronic Thermal 
Characteristic 
30–600 sec.  60 
 
06.08  Present Fault Record  0: No fault 
0 
 
06.09 
Second Most Recent 
Fault Record 
1: Over current (oc) 
2: Over voltage (ov) 
06.10 
Third Most Recent Fault 
Record 
3: IGBT Overheat (oH1) 
5: Overload (oL) 
06.11 
Record 
6: Overload1 (oL1) 
7: Motor overload (oL2) 
06.12 
Fifth Most Recent Fault 
Record 
8: External fault (E.F.) 
9: Current exceeds two times the rated current  
 
 
during acceleration (ocA) 
   
10: Current exceeds two times the rated current  
   during deceleration (ocd) 
   
11: Current exceeds two times the rated current 
   during constant speed operation (ocn) 
 
   
    14: Phase-Loss (PHL)   
16: Auto-acceleration / auto-deceleration failure 
   (CFA) 
 
17: Software / Password protection (codE)   
18: Power Board CPU WRITE failure (cF1.0)   
19: Power Board CPU READ failure (cF2.0)   
20: CC, OC Hardware protection failure (HPF1)   
    21: OV Hardware protection failure (HPF2)