Chapter 12 Description of Parameter SettingsC2000-HS
12.1-02-19
Settings Functions Descriptions
65
Output for both
CANopen and RS-485
control
To control output of CANopen & InnerCOM internal
communication.
66 SO output logic A (N.O.)
Status of
the drive
Status of safety output
Status A (MOx=66) Status B (MOx=68)
Normal Broken circuit (Open) Short circuit (Close)
STO Short circuit (Close) Broken circuit (Open)
STL1–STL3 Short circuit (Close) Broken circuit (Open)
68 SO output logic B (N.C.)
67
Analog input level
reached
The multi-function output terminals operate when the analog input
level is between the high level and the low level.
Pr.03-44: Select one of the analog input channels (AVI, ACI and
AUI) to be compared.
Pr.03-45: The high level for the analog input, default is 50%.
Pr.03-46: The low level for the analog input, default is 10%.
If analog input > Pr.03-45, the multi-function output terminal
operates. If analog input < 03-46, the multi-function output
terminal stops output.
70
FAN warning detection
output
The terminal works when the internal fan warning activates.
Example: Crane Application
It is recommended to use with Dwell function as shown in the following: