EasyManua.ls Logo

Delta VFD1100C43A-HS

Delta VFD1100C43A-HS
814 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 12 Description of Parameter SettingsC2000-HS
12.1-03-26
The requirement for these three parameters (Pr. 03-69, Pr. 03-71 and Pr. 03-73) is Pr. 03-69 < Pr.
03-71 < Pr. 03-73. The values for three proportional points (Pr. 03-70, Pr. 03-72 and Pr. 03-74)
have not limits. Values between two points are calculated by a linear calculation
.
The output % becomes 0% when the negative AUI input value is lower than the lowest point
setting. For example:
Pr. 03-69 = -1V; Pr. 03-70 = 10%, then the output becomes 0% when the AUI input is ≥ -1V. If the
AUI input varies between -1 V and -1.1 V, the drive’s output frequency oscillates between 0%
and 10%.

Table of Contents

Related product manuals