Chapter 12 Description of Parameter SettingsC2000-HS
12.1-05-6
Accumulated Motor Operation Time (Min)
Default: 0
Settings
0
1439
Accumulated Motor Operation Time (Day)
Default: 0
Settings
0
65535
Use Pr. 05-31 and Pr. 05-32 to record the motor operation time. To clear the operation time, set Pr.
05-31 and Pr. 05-32 as 00. An operation time shorter than 60 seconds is not recorded.
Induction Motor (IM) or Permanent Magnet Synchronous Motor Selection
Default: 0
Settings 0: IM (Induction Motor)
1: SPM (Surface permanent magnet motor)
2: IPM (Interior permanent magnet motor)
Full-load current for a Permanent Magnet Motor
Default: Depending
on the model power
Settings Depending on the model power
Sets the full-load current for the motor according to motor’s nameplate. The default is 90% of the
drive’s rated current.
For example: The rated current of a 7.5 HP (5.5 kW) is 25 A. The default is 22.5A.
The setting range is between 40%
120% of rated current.
25*40 %=10 A and 25*120 %=30 A
Rated Power for a Permanent Magnet Motor
Default: Depending on
the model power
Settings
0.00
655.35 kW
Sets the rated power for the permanent magnet synchronous motor. The default is the drive’s
power value.
Rated speed for a Permanent Magnet Motor
Default: 2000
Settings
0
65535 rpm
Pole number for a Permanent Magnet Motor
Default: 10
Settings
0
65535
System Inertia for a Permanent Magnet Motor
Default: Depending
on the motor power
Settings
0.0
6553.5 kg-cm
2
Default values are as below: