Chapter 12 Description of Parameter SettingsC2000-HS
12.1-06-18
Status 4: The drive is in STOP; Pr. 06-48 ≠ 0; Pr. 07-02 = 0
When the drive starts, it executes Pr. 06-48 as the DC brake. The DC brake current level is 20
times the Pr. 06-47 setting value. In this period, if an OPHL happens within the time for Pr. 06-48,
the drive executes the Pr. 06-45 setting after the drive starts counting for half the time of Pr.06-48.
Status 4-1: Pr. 06-48 0, Pr. 07-02 = 0 (No OPHL detected before operation)
Status 4-2: Pr. 06-48 0, Pr. 07-02 = 0 (OPHL detected before operation)
LvX Auto-reset
Default: 0
Settings 0: Disable
1: Enable
Time for Input Phase Loss Detection
Default: 0.20
Settings 0.00–600.00 sec.