Chapter 12 Description of Parameter SettingsC2000-HS
12.1-09-16
Firmware Version of Communication Card
Default: Read only
Settings Read only
Product Code
Default: Read only
Settings Read only
Error Code
Default: Read only
Settings Read only
Communication Card Address (for DeviceNet and PROFIBUS)
Default: 1
Settings DeviceNet: 0–63
Profibus-DP: 1–125
Communication Card Speed Setting (for DeviceNet)
Default: 2
Settings Standard DeviceNet:
0: 125Kbps
1: 250Kbps
2: 500Kbps
3: 1Mbps (Delta only)
Non-standard DeviceNet: (Delta only)
0: 10Kbps
1: 20Kbps
2: 50Kbps
3: 100Kbps
4: 125Kbps
5: 250Kbps
6: 500Kbps
7: 800Kbps
8: 1Mbps
Other Communication Card Speed Setting (for DeviceNet)
Default: 0
Settings 0: Standard DeviceNet
In this mode, the baud rate can only be 125Kbps, 250Kbps, and 500Kbps
in standard DeviceNet speed.
1: Non-standard DeviceNet
In this mode, the baud rate of DeviceNet can be the same as that for
CANopen (0–8).
Use with Pr. 09-71.
0: The baud rate can only be set to 125Kbps, 250Kbps and 500Kbps.
1: The DeviceNet communication rate can be the same as that for CANopen (setting 0–8).